Knowledge base

Why does a marine heat exchanger lose thermal fficiency? The Role of Biofouling Explained

A heat exchanger does not have to be defective to perform below its expected capacity. In practice, we regularly see the cooling capacity of heat exchangers on board vessels gradually decline. Cooling water temperatures increase, engines run hotter, and the pressure drop across the heat exchanger rises. In many cases, these issues are not caused by a mechanical failure, but by fouling on the seawater side of the heat exchanger.

During inspections of marine heat exchangers, biofouling is one of the most common causes of reduced thermal efficiency. This is particularly true for systems using seawater, such as Central Cooling Systems, Jacket Water Coolers, and Lube Oil Coolers, where biological contamination can build up unnoticed over time.

In this article, we explain how biofouling develops, why it reduces heat transfer, and how timely maintenance can help prevent unplanned downtime.

What is thermal efficiency?

Thermal efficiency describes how effectively a heat exchanger transfers heat from one medium to another. The more efficiently heat is transferred, the better the heat exchanger performs and the more stable the operating temperatures remain for engines, lubricating oil, or cooling water systems.

In a clean heat exchanger, the process fluid is in direct contact with the metal surface of the plates or tubes, allowing heat to be transferred efficiently.

However, once even a thin layer of fouling develops, it creates additional thermal resistance between the fluid and the metal surface. A relatively thin layer of biofilm or deposits can significantly reduce heat transfer. As a result, the heat exchanger has to work harder to remove the same amount of heat, leading to a loss of thermal efficiency.

What is biofouling?

Biofouling is the accumulation of living organisms on wet surfaces. In marine heat exchangers, this process usually starts with a thin biofilm consisting of bacteria and microorganisms. This sticky biofilm then provides an ideal surface for algae, organic debris, mussels, barnacles and other marine organisms to attach.

Unlike mineral deposits, biofouling develops through biological activity. Because of this, it often builds up gradually and remains unnoticed for an extended period.

Over time, the biofilm also traps other contaminants such as sand, silt and corrosion particles. This creates an increasingly thicker insulating layer that restricts flow and reduces heat transfer.

The impact of biofouling on thermal efficiency

The primary function of a heat exchanger is to transfer heat efficiently. When biofouling develops on plates or tubes, it forms an insulating barrier between the metal surface and the cooling medium. This significantly reduces heat transfer performance.

In practice, we regularly see multiple issues reinforcing one another:

  • reduced heat transfer;
  • decreased cooling capacity;
  • increased pressure drop across the heat exchanger;
  • reduced system flow and increased pump load;
  • higher engine and cooling water temperatures;
  • increased fuel consumption as systems operate less efficiently.

Biofouling also increases the risk of corrosion. Oxygen concentration differences beneath the biofilm can accelerate localized corrosion. If left untreated, this may eventually result in damaged plates, leakage or even complete heat exchanger failure.

How can you recognize biofouling?

Biofouling usually develops gradually, which means the first warning signs are not always immediately linked to the heat exchanger itself.

Common indicators include:

  • increasing cooling water temperatures;
  • higher engine operating temperatures;
  • reduced cooling capacity;
  • increased pressure drop across the heat exchanger;
  • frequent temperature or pressure alarms;
  • rising energy or fuel consumption.

If several of these symptoms occur simultaneously, it is advisable to inspect the heat exchanger before performance deteriorates further.

What is the difference between biofouling and scaling?

Although the terms are often used interchangeably, biofouling and scaling are two different types of fouling.

Biofouling consists of living organisms such as bacteria, biofilm, algae and shellfish.

Scaling refers to mineral deposits, such as calcium carbonate or salt crystals, that precipitate due to temperature changes or variations in water chemistry.

Both types of fouling reduce heat transfer efficiency, but they do not always require the same cleaning approach. The most effective cleaning method depends on both the type of deposit and the construction material of the heat exchanger.

When Should a Heat Exchanger Be Cleaned?

One of the most common mistakes is waiting until a heat exchanger can no longer provide sufficient cooling capacity or causes a system failure.

Because biofouling develops gradually, preventive maintenance is often far more effective than waiting until performance has already declined significantly.

During inspections of marine heat exchangers, we typically assess:

  • the extent of fouling;
  • heat transfer performance;
  • pressure drop;
  • the condition of plates or tubes;
  • signs of corrosion or mechanical damage.

Based on these findings, it can be determined whether cleaning is sufficient or if further maintenance is required.

Cleaning options: chemical cleaning or ultrasonic cleaning

The appropriate cleaning method depends on both the type of heat exchanger and the nature of the fouling.

Chemical cleaning, also known as Cleaning-In-Place (CIP), is particularly suitable when deposits are chemically removable and the heat exchanger does not need to be dismantled. Typical applications include light to moderate fouling, biological contamination, grease, oil, limescale, rust and other forms of scaling. During this rapid inline cleaning process, a suitable cleaning solution is circulated through the heat exchanger to dissolve and remove deposits. The cleaning chemicals used depend on the type of contamination. Different products are applied for biological and organic fouling than for mineral deposits such as calcium carbonate and rust.

Ultrasonic cleaning is used when fouling is located in difficult-to-access areas or cannot be completely removed by mechanical or chemical cleaning alone. This method is particularly effective for biofouling, salt deposits, sludge and other stubborn contaminants found in plate heat exchangers, bundles, marine coolers and oil coolers. High-frequency ultrasonic vibrations loosen deposits from surfaces and narrow passages that are difficult to reach using conventional cleaning methods.

Depending on the condition of the heat exchanger, we regularly apply a combination of both cleaning methods to achieve the best possible cleaning result.

 

When is heat exchanger overhaul required?

Not every heat exchanger can be restored by cleaning alone.

If inspection reveals damaged plates, worn gaskets or leakage caused by corrosion, heat exchanger overhaul is often the most sustainable solution.

Overhaul may include:

  • inspection of plates and tubes;
  • gasket replacement;
  • corrosion and wear assessment;
  • pressure testing;
  • reassembly and final performance testing.

 

This not only restores the performance of the heat exchanger itself but also improves the reliability of the entire cooling system.

 

Conclusion

Marine heat exchangers rarely lose thermal efficiency overnight. In most cases, performance gradually declines due to biofouling, scaling or other deposits on the seawater side of the heat exchanger.

By recognizing early warning signs—such as rising cooling water temperatures, increasing pressure drop and reduced cooling capacity—maintenance can be scheduled before unplanned downtime occurs. Depending on the type of fouling, chemical cleaning, ultrasonic cleaning or a combination of both methods can restore much of the original performance. Where wear, leakage or corrosion are identified, refurbishment is often the logical next step.

At Blue Orange, we see every day how timely inspection and the right maintenance strategy contribute to the reliable operation of marine heat exchangers. By carefully analysing the type of fouling and selecting the most appropriate treatment, the service life of the heat exchanger can be extended while maintaining optimum cooling performance.

Biofouling cannot be completely prevented in marine environments. Seawater naturally contains microorganisms that attach to wet surfaces and gradually form biofilms. However, regular inspections, preventive maintenance and timely cleaning can significantly reduce the build-up of biofouling and help maintain the thermal efficiency of a marine heat exchanger.

Biofouling mainly affects heat exchangers that operate with seawater, either directly or indirectly. This includes plate heat exchangers, shell & tube heat exchangers, Jacket Water Coolers, Lube Oil Coolers and heat exchangers used in Central Cooling Systems. The rate of fouling depends on factors such as water quality, operating conditions and maintenance intervals.

The cost of heat exchanger refurbishment depends on several factors, including the type and size of the heat exchanger, the extent of fouling or damage, and whether components such as plates or gaskets need to be replaced. In many cases, refurbishment is a more cost-effective alternative to replacing the entire heat exchanger. Following an inspection, the required work can be assessed and an accurate quotation can be provided based on the actual condition of the unit.

Yes. As biofouling reduces heat transfer, cooling systems become less efficient. Pumps may have to work harder, cooling capacity decreases and engines can operate at higher temperatures. Depending on the system and operating conditions, this can lead to increased energy use and higher fuel consumption.

If left untreated, biofouling can increase the risk of localized corrosion beneath the biofilm. Over time, this may damage plates, tubes or gaskets, eventually leading to leaks or reduced reliability. Timely inspection and cleaning help minimise the risk of permanent damage and extend the service life of the heat exchanger.

Not every type of fouling requires the same treatment. An inspection helps identify the nature and severity of the contamination, allowing the most appropriate cleaning method to be selected. This ensures effective cleaning while avoiding unnecessary wear or damage to the heat exchanger.

Need Help with Heat Exchanger Refurbishment?

Not sure whether your heat exchanger requires refurbishment? Or would you rather address a developing issue before it leads to unplanned downtime?

At Blue Orange, we combine practical experience with technical expertise. We provide inspections, technical advice and refurbishment solutions tailored to marine heat exchangers, your installation and your maintenance schedule. No one-size-fits-all approach—just clear recommendations based on the actual condition of your equipment.

Feel free to contact us to discuss the condition of your heat exchanger. Together, we’ll determine the most suitable solution to keep your cooling system operating reliably—both now and in the long term.