A small leak along the plate pack may be the first visible sign that the sealing of a plate heat exchanger is no longer reliable. Sometimes the gaskets have hardened or become damaged. In other cases, the cause may be a deformed plate, corrosion, incorrect assembly or a problem with the compression of the plate pack.
Simply looking at the point where the leak appears is therefore not enough. The gaskets do more than seal the heat exchanger. They also determine how the hot and cold media flow through the individual channels. A damaged, displaced or incorrectly installed gasket can therefore affect the safety, performance and operational reliability of the installation.
Installing new gaskets also provides no certainty if the plates or gasket grooves are damaged. Only after cleaning, inspection, correct assembly and an appropriate pressure and leak test can it be established whether the plate pack is ready for reliable operation again.
In this article, we explain how to recognise worn gaskets, what causes them to become damaged and how a professional replacement and reconditioning process is carried out.
What is the function of the gaskets?
A plate heat exchanger consists of a pack of thin, profiled plates. Narrow channels are formed between these plates, through which the hot and cold media flow. The gaskets are fitted into specially shaped grooves along the edges and around the port openings of each plate.
They perform two important functions. First, they seal the spaces between the plates, preventing the medium from leaking to the outside. Second, they direct the media through separate channels. Depending on the position and shape of the gaskets, the hot medium flows through one channel and the cold medium through the adjacent channel.
Heat is transferred through the thin plate material without the two media coming into contact with each other. The gaskets are therefore more than simple rubber seals. They are an important part of the flow pattern and the separation between the two circuits.
If a gasket shifts, cracks or is not seated correctly in its groove, external leakage may occur. Damage to the plates or sealing surfaces can also result in internal leakage, allowing the two media to mix.
When should the gaskets be replaced?
There is no fixed service life that applies to every plate heat exchanger. The condition of the gaskets depends on factors such as temperature, pressure, process media, cleaning agents, operating hours and the number of heating and cooling cycles.
Several signs may indicate that replacement is necessary.
One of the clearest signs is visible leakage along the side or underneath the plate pack. Leakage during a cold start may also indicate ageing gaskets. In this case, the rubber is no longer sufficiently elastic to seal immediately, but may expand slightly as the heat exchanger warms up.
When a heat exchanger has been opened, worn gaskets can often be recognised by:
- hard, dry or cracked surfaces;
- missing pieces of rubber;
- gaskets that have moved out of their grooves;
- swollen or deformed sections;
- gaskets hanging loosely from the plate;
- adhesive bonds that have come loose;
- gaskets that break under light pressure.
Recurring leakage after retightening the plate pack is another important warning sign. Tightening the plate pack further is not automatically the correct solution. If the plate pack is compressed beyond the specified dimension, the plates, gaskets and even the frame may be damaged.
The cause of the leakage must therefore be established first.
What causes gaskets to wear?
Gaskets are made from elastomers. These materials are flexible, but they are continuously exposed to stress during operation.
High temperatures, for example, accelerate the ageing process of rubber. This is particularly relevant when an installation is frequently heated up and cooled down. The gaskets repeatedly expand and contract and may eventually lose their elasticity.
Pressure fluctuations also play a role. Valves that are opened too quickly, pump starts or blockages can cause pressure surges. These may push a gasket out of its groove or overload it locally.
Chemical attack is another common cause. Not every gasket material is resistant to every medium. A gasket may swell, soften, shrink or dissolve if the material is unsuitable for the process fluid or cleaning agent being used.
Changes in operating conditions can also have an effect. A gasket that has performed reliably for years is not automatically suitable if the operating temperature is increased, a different medium is introduced or the cleaning procedure changes.
Damage may also occur during maintenance. Examples include dirt in the gasket groove, incorrectly positioned gaskets, insufficiently cured adhesive or a plate pack that has been tightened unevenly.
It is therefore important not only to replace the damaged gasket, but also to investigate why it became damaged. This helps to reduce the risk of the same problem recurring.
Is the gasket the only defective component?
Leakage along the plate pack is often quickly attributed to a defective gasket. However, the same problem can have several different causes.
Possible causes include:
- small cracks or pinholes in a plate;
- pitting corrosion;
- erosion caused by high flow velocities or contamination;
- deformed plates;
- damaged or worn gasket grooves;
- plates installed in the wrong direction;
- an incorrect plate sequence;
- uneven compression;
- a plate pack that is too loose or too tightly compressed.
A new gasket cannot seal a damaged plate
This is precisely why thorough cleaning is so important. Small cracks, corrosion and deformation are often barely visible on heavily contaminated plates. Only after deposits, oil, scale, sludge and old adhesive residues have been removed can the material be assessed reliably.
Installing new gaskets on plates that have not been inspected properly may result in the heat exchanger leaking again after assembly. In that case, the entire plate pack has to be opened and rebuilt once more, leading to additional downtime and costs.
How are gaskets in a plate heat exchanger replaced?
At Blue Orange, gasket replacement is part of a complete inspection of the plate pack. New gaskets are not simply installed straight away. The plates are cleaned and inspected first, ensuring that any damage does not go unnoticed.
1. Receipt and registration
When the heat exchanger or loose plate pack arrives at our workshop, we record the key information and its current condition. We inspect the manufacturer, type, number of plates, plate material, existing gaskets and any visible contamination or damage.
For a complete heat exchanger, we also record the plate sequence and tightening dimension.
2. Dismantling and removing the old gaskets
A complete heat exchanger is opened in a controlled manner and the plate pack is dismantled. During this process, we carefully record the sequence and orientation of the plates.
The old gaskets are then removed. With glued gaskets, the adhesive residues are also removed without damaging the thin plates or gasket grooves.
3. Cleaning the plates and gasket grooves
The plates are cleaned thoroughly. The cleaning method is adapted to the plate material and the type of contamination, such as scale, oil, rust, sludge or process deposits.
The gasket grooves are also cleaned completely. Remaining dirt, grease or adhesive can prevent a new gasket from fitting correctly.
4. Inspecting every plate
After cleaning, we inspect each plate individually for cracks, pinholes, corrosion, deformation and damaged gasket grooves.
Small defects are not always immediately visible. Additional dye penetrant testing or another suitable inspection method may therefore be used. Plates that can no longer be used reliably are replaced.
5. Installing the new gaskets
The new gaskets must suit both the plate type and the application. We consider the medium, temperature, pressure, cleaning agents and manufacturer specifications.
Clip-on gaskets are carefully fitted into the grooves. With glued gaskets, we ensure that the surface is clean, the correct adhesive is used and sufficient curing time is allowed.
6. Rebuilding the plate pack
Once the gaskets have been installed, we rebuild the plate pack in the correct sequence and orientation. We check the flow pattern, gasket positioning and plate alignment.
For a complete heat exchanger, the plate pack is tightened evenly to the specified dimension.
7. Testing and reporting
Finally, the heat exchanger is hydraulically tested for external leakage and leakage between the circuits. The test procedure is adapted to the type of heat exchanger and its technical specifications.
After the final inspection, the work carried out and the test results are recorded, and the heat exchanger is prepared for return delivery.
Clip-on or glued gaskets
With glue-free or clip-on gaskets, the gasket is mechanically attached to the plate. Installation is generally faster and no curing time is required. However, this does not mean that the positioning requires less accuracy. A clip that has not fully engaged or a twisted gasket may still cause leakage.
Glued gaskets are secured in the gasket groove using a suitable adhesive. The groove must be very clean and properly prepared. The choice of adhesive and the curing conditions are also important.
The plate type, gasket design and manufacturer specifications determine which method is used. One method is therefore not automatically better than the other in every situation.
Replacing the gaskets or reconditioning the complete heat exchanger?
Replacing only the gaskets may be appropriate when the plates are clean and demonstrably in good condition, the cause can clearly be attributed to the gaskets and there are no indications of internal leakage.
The gasket grooves must also be undamaged, and the correct plate sequence and tightening dimension must be known.
A complete reconditioning process is more appropriate when:
- the heat exchanger is heavily contaminated;
- the cause of the leakage is unclear;
- maintenance has been postponed for a long time;
- corrosion, wear or deformation is visible;
- mixing between the two media may be occurring;
- the heat exchanger is part of a critical process;
- unplanned downtime would have major consequences.
When the plate pack is fully opened, it is a logical moment to inspect not only the gaskets but also the condition of every plate. This prevents new gaskets from being installed on a plate pack that is already damaged elsewhere.
In need of a complete heat exchanger haul? Click here.
The role of Blue Orange
Blue Orange does not treat gasket replacement as an isolated repair. We inspect the complete plate pack, investigate the cause of the leakage and test the heat exchanger before it is returned to service.
The process begins with a technical inspection and diagnosis. We look beyond the visible defect. Has the gasket aged, been chemically attacked or been pushed out of its groove? Or is the leakage caused by a damaged plate, deformation or incorrect assembly?
The plate pack is then dismantled and the plates are cleaned individually. Only when the surface is properly clean can cracks, fractures, corrosion and damage to the gasket grooves be assessed carefully.
Where necessary, damaged plates and worn gaskets are replaced. When selecting new gaskets, we take account of the heat exchanger type and the conditions in which it operates.
The plate pack is then rebuilt in the correct sequence and tightened evenly. Finally, Blue Orange carries out a hydraulic pressure test. The work performed and the test results are recorded in a report after the final inspection.
This means that the customer receives more than a heat exchanger fitted with new gaskets. They receive an inspected and tested plate pack prepared for reliable operation.
How can premature gasket damage be prevented?
Not every form of wear can be prevented. However, appropriate operating practices and maintenance can reduce the risk of premature damage.
Always use a gasket material that is suitable for the medium, temperature and cleaning method. Reassess this choice when the process conditions change.
Open and close valves gradually to reduce sudden pressure differences and water hammer. A controlled start-up also helps reduce thermal and mechanical stress on the gaskets.
Only use cleaning agents and concentrations that are suitable for both the plates and the gaskets. An overly aggressive cleaning process can quickly damage a seal that previously appeared to be functioning correctly.
Have minor leaks investigated promptly and record completed maintenance work, replacement dates and deviations in pressure or temperature. This makes it easier to identify patterns and plan maintenance around scheduled shutdowns.
Prevent a small leak from causing downtime
Gaskets are essential to both the sealing and flow pattern of a plate heat exchanger. Over time, temperature, pressure, process media and natural ageing cause them to lose their elasticity and reliability.
However, leakage does not automatically mean that only the gaskets need to be replaced. The plates, gasket grooves, plate sequence and compression of the plate pack must also be checked.
Blue Orange therefore cleans and inspects the complete plate pack, replaces damaged components where necessary and tests the heat exchanger after assembly.
Is your plate heat exchanger leaking, or are you unsure about the condition of its gaskets? Have the plate pack assessed in time, before a small leak results in unplanned downtime.
There is no universal replacement interval. Service life depends on the gasket material, medium, temperature, pressure, cleaning method, operating hours and the number of thermal cycles. The condition of the gaskets and the operating environment are therefore more important than age alone.
Not without first checking the cause and the current tightening dimension. Excessive tightening may damage the gaskets, plates and frame. Leakage may also be caused by corrosion, deformation or incorrect plate assembly.
Old gaskets that have hardened, become deformed, suffered damage or come loose are generally not reliable enough to reuse. Even when gaskets still appear to be in good condition, they may no longer be elastic enough to seal properly after the plate pack has been opened.
During a complete reconditioning process, replacing all gaskets in the plate pack at the same time is generally the most reliable approach. Combining old and new gaskets may result in differences in elasticity, thickness and compression.
Because leakage is not always caused by the gaskets. Cracks, pinholes, corrosion, deformation and damaged gasket grooves may cause similar problems. A new gasket will not solve these defects.
After reassembly, an appropriate pressure and leak test is carried out. The exact test method and pressure depend on the heat exchanger, its nameplate, the OEM instructions and the technical requirements of the application.
Need Help with Heat Exchanger Refurbishment?
Not sure whether your heat exchanger requires refurbishment? Or would you rather address a developing issue before it leads to unplanned downtime?
At Blue Orange, we combine practical experience with technical expertise. We provide inspections, technical advice and refurbishment solutions tailored to marine heat exchangers, your installation and your maintenance schedule. No one-size-fits-all approach—just clear recommendations based on the actual condition of your equipment.
Feel free to contact us to discuss the condition of your heat exchanger. Together, we’ll determine the most suitable solution to keep your cooling system operating reliably—both now and in the long term.